Earthing Systems Explained: TN-S, TN-C-S (PME) and TT

TN-S, TN-C-S (PME) and TT earthing explained with a simple diagram: how to recognise each, why it matters for EV chargers and outbuildings, and what to record.

4 min read · 21 November 2026 · RoomPlot Team

Every electrical installation needs a path to earth, so that a fault blows a fuse or trips a breaker instead of making metalwork live. In the UK that path comes in three main forms. Knowing which one a property has shapes decisions about EV chargers, outbuildings and RCDs.

EARTHING SYSTEMSTN-S, TN-C-S and TT at a glance TN-S Supply Home L N PE Separate earth from the supplier Usually the metal sheath of the supply cable TN-C-S (PME) Supply Home L PEN Neutral and earth combined in the supply They split at the service head TT Supply Home L N Earth rod Your own earth electrode No earth from the supplier. RCDs are essential
The three common arrangements. The difference is where the earth connection comes from.

Key takeaways

  • TN-S: the supplier provides a separate earth, usually the metal sheath of the supply cable.
  • TN-C-S, also called PME: neutral and earth share one conductor in the supply and split at the service head.
  • TT: there is no earth from the supplier, so the installation uses its own earth electrode and relies on RCDs.
  • The earthing system affects EV charger installation and how outbuildings are supplied.

What the letters mean

The first letter describes the supply: T means the supply is connected directly to earth at the transformer. The second describes the installation: N means its metalwork is connected to the supply's earthed point, and T means it is connected to its own electrode in the ground. S and C say whether neutral and protective conductors are separate or combined.

TN-S

The protective conductor is separate from the neutral all the way back to the transformer. In older properties it is typically the lead sheath of the service cable, with an earth clamp at the service head. It gives a reliable, low-resistance earth, although ageing cable sheaths can degrade.

TN-C-S (PME)

The most common arrangement in newer UK supplies. One conductor serves as both neutral and earth in the network, and the two are separated at the service head. It is cheap for the network and gives a very low earth fault loop impedance. The weak point is a broken combined conductor: metalwork connected to the earth can then rise towards mains voltage. That risk is why extra measures apply to EV charging points and why care is needed when taking this earth outdoors.

TT

Common in rural areas with overhead supplies. The installation has its own earth electrode, usually a rod driven into the ground. The earth path has a higher resistance, so overcurrent devices alone cannot be relied on to clear an earth fault. RCDs do that job.

Stay safe. Never open or interfere with the service head or cut-out. It belongs to the network operator. If you cannot tell which earthing system a property has, a registered electrician or the network operator can confirm it.

Why it matters for a design

  • EV chargers. On a PME supply, a charging point needs protection against an open combined conductor, built into many chargers, or its own earth electrode.
  • Outbuildings. The designer decides whether to extend the house earth or make the outbuilding a TT installation with its own rod.
  • Bonding. Main protective bonding to gas, water and other metal services is sized for the earthing system.

Record it on the plan

Write the earthing system next to the consumer unit on your plan, along with the position of the main earthing terminal and any earth electrode. It is a line of text in RoomPlot, and it saves the next electrician twenty minutes of detective work.

Frequently asked questions

How can I tell which earthing system I have?

The clues are at the service head: an earth clamp on the cable sheath suggests TN-S, an earth wire from the service head terminal with a PME label suggests TN-C-S, and an earth wire running to a rod outside suggests TT. An electrician can confirm it by inspection and testing.

Is PME safe?

Yes. It is the standard arrangement for most new supplies. The additional rules for EV charging and outdoor equipment deal with the rare case of a broken combined conductor.

Can I convert from TT to PME?

Only the network operator can provide a PME earth terminal. They decide whether it is available at your property.

Free lesson. Want the full picture? UK rules for electrical plans is part of our free electrical floor plans course, with interactive exercises.

Sources

Plan it on your phone. Note the earthing system, the consumer unit and every circuit on a plan you can hand to the next person. Download RoomPlot on the App Store and draw your first electrical plan in minutes, or see what it does on our electricians page.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read