Lesson 10 of 18 All lessons
- 1What an electrical floor plan is, and who uses it
- 2Electrical symbols: lights, switches, sockets and distribution
- 3Circuits explained: lighting, rings, radials and dedicated supplies
- 4Drawing the base plan: measuring, doors and fixed fittings
- 5Lighting and switching: one-way, two-way and intermediate
- 6Sockets and spurs: how many, where, and on which circuit
- 7Kitchens and bathrooms: special rules for special rooms
- 8Cable routes, lengths and circuit schedules
- 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
- 10UK rules: BS 7671, Part P and what applies where
- 11UK protection: consumer units, RCD types and surge protection
- 12UK earthing systems, mounting heights and certificates
- 13US rules: the NEC, receptacle spacing, GFCI and AFCI
- 14US kitchens and bathrooms: receptacle rules on the plan
- 15US panels, GFCI, AFCI and wire sizes
- 16Worked example: from survey to a finished plan
- 17Checking your plan and handing it over
- 18Final test: check what you have learned
In this lesson
- BS 7671:2018+A4:2026 is the current wiring standard.
- New circuits, consumer units and bathroom work are usually notifiable in England.
- Rented homes need an EICR at least every five years.
In the UK, electrical plans describe installations that must follow BS 7671 and, in England, the Building Regulations. This lesson is your map of the rules that matter for domestic work.
BS 7671, the IET Wiring Regulations
BS 7671:2018+A4:2026 is the current edition. Amendment 4 adds a chapter on stationary batteries, a section on Power over Ethernet and major changes to medical locations. Key domestic points include 30 mA RCD protection for most socket circuits up to 32 A, AFDDs in HMOs and higher-risk residential buildings, and Section 701 for bathrooms.
Part P (England)
New circuits, consumer unit replacements and new work in rooms with a bath or shower are usually notifiable, through a registered competent person, a third-party certifier or building control.
Accessibility
For new dwellings in England, Approved Document M points switches and sockets to between 450 mm and 1200 mm above the finished floor.
Rented homes
Private landlords, and now social landlords, must have the installation inspected at least every five years and act on C1, C2 and FI findings within 28 days.
Alarms
Domestic fire alarms follow BS 5839-6, with grades and categories that decide where alarms go; landlords in England also have smoke and carbon monoxide alarm duties.
Wales, Scotland and Northern Ireland have their own building standards. BS 7671 applies across the UK.
Try it
Write down three jobs: a new kitchen circuit, a replacement light switch and a new shower. Which are notifiable in England?