Lesson 9 of 18 All lessons
- 1What an electrical floor plan is, and who uses it
- 2Electrical symbols: lights, switches, sockets and distribution
- 3Circuits explained: lighting, rings, radials and dedicated supplies
- 4Drawing the base plan: measuring, doors and fixed fittings
- 5Lighting and switching: one-way, two-way and intermediate
- 6Sockets and spurs: how many, where, and on which circuit
- 7Kitchens and bathrooms: special rules for special rooms
- 8Cable routes, lengths and circuit schedules
- 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
- 10UK rules: BS 7671, Part P and what applies where
- 11UK protection: consumer units, RCD types and surge protection
- 12UK earthing systems, mounting heights and certificates
- 13US rules: the NEC, receptacle spacing, GFCI and AFCI
- 14US kitchens and bathrooms: receptacle rules on the plan
- 15US panels, GFCI, AFCI and wire sizes
- 16Worked example: from survey to a finished plan
- 17Checking your plan and handing it over
- 18Final test: check what you have learned
In this lesson
- A big or fixed load gets its own circuit from the consumer unit or panel.
- Current is power divided by voltage: that number starts every design.
- Draw each dedicated circuit in its own colour, with its isolator and its length.
Most points in a home share a circuit with their neighbours. A few loads are too big, or too important, to share. They get a dedicated circuit: one cable, one protective device, one job. This lesson shows how to spot them and how to draw them.
What makes a circuit dedicated
- A large load: electric showers, cookers, EV chargers, heat pumps, immersion heaters.
- A load that runs for hours, such as vehicle charging.
- A supply to another building: a garage, shed or garden office.
- The manufacturer says so. The installation instructions always win.
From power to current
Every design starts with one sum: current = power / voltage. A 9.5 kW shower on a 230 V supply draws about 41 A. A 7.4 kW EV charger draws about 32 A. In the US, loads that run for three hours or more are sized at 125%, which is why a 48 A charger needs a 60 A circuit.
Electric showers
A shower has its own circuit, a 30 mA RCD and a double-pole isolator: a ceiling pull cord in the bathroom or a wall switch outside it. 10 mm² cable is the common choice in the UK, confirmed by the designer for the route and length.
Cookers
Cookers rarely run flat out, so designers apply diversity: in UK guidance, the first 10 A plus 30% of the rest. That is how a 12 kW cooker sits on a 32 A circuit. The cooker switch goes within 2 m of the appliance and never directly above the hob.
EV chargers
Draw the car first, then put the charger where its lead reaches the charge port. A UK 7.4 kW charger usually has a 32 A circuit with protection against DC fault currents. A US Level 2 charger follows the 125% rule above.
Outbuildings
A supply to a garden building is a small installation in itself: an armoured cable, a local consumer unit and an earthing decision for the designer. The route length matters, because voltage drop grows with distance.
Draw it
Give each dedicated circuit its own colour and label it with the load, the device and the cable, for example "C6 EV charger, 32 A, 6 mm²". Mark the isolator. Read the length from the route.
Free calculators for this lesson: breaker size calculator, watts to amps calculator, cooker diversity calculator, EV charging time calculator.
Try it
List the three biggest electrical loads in your home. For each one, find its rating plate, work out the current and check whether it has its own circuit.