Electrical

Cooker Diversity Calculator

A cooker is never fully on for long. Enter its total rating to see the current to design the circuit for.

Calculator
Cooker control unit

Fill in the fields above to see results.

How it works

The IET On-Site Guide allowance for household cooking appliances is the first 10 A of the rated current, plus 30% of the remainder, plus 5 A if the cooker control unit has a socket outlet. Add the oven and hob ratings together when they share a circuit. Induction hobs and some ovens have their own circuit requirements, so the manufacturer instructions come first.

Frequently asked questions

Can a 12 kW cooker go on a 32 A circuit?

Usually, yes. 12 kW is about 52 A at 230 V. With diversity that is 10 A plus 30% of the remaining 42 A: about 22.7 A, or 27.7 A with a socket on the control unit, which is inside 32 A.

Does diversity apply to induction hobs?

The same allowance is commonly applied, but some manufacturers specify a circuit rating for their appliance. Where they do, follow it.