Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch

UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it.

3 min read · 21 November 2026 · RoomPlot Team

An electric cooker can be rated at 10 kW or more, yet it usually runs happily on a 32 A circuit. The reason is diversity: the rings and oven are never all at full power for long. This guide explains the sum, the cable and where the switch goes.

C4 Kitchen Cooker circuit One dedicated radial CIRCUITS (CABLE ROUTES) C4 Cooker 6 mm² · 32 A RCBO SYMBOLS Cooker Control Unit Consumer Unit
The cooker circuit on a kitchen plan: one radial from the consumer unit to a cooker control unit beside the hob.

Key takeaways

  • A cooker has its own radial circuit from the consumer unit.
  • Diversity lets the designer assume less than the full rated current: 10 A plus 30% of the rest.
  • A 32 A circuit in 6 mm² cable suits most domestic cookers, subject to the route and length.
  • The cooker switch goes within 2 m of the appliance and not directly above the hob.

The diversity sum

The IET On-Site Guide gives a simple allowance for household cooking appliances: take the first 10 A of the rated current, add 30% of the remainder, and add 5 A if the cooker control unit includes a socket.

For a 12 kW cooker: 12,000 W divided by 230 V is about 52 A. Applying diversity gives 10 A plus 30% of 42 A, which is 22.6 A. Even with a socket on the control unit that is under 28 A, so a 32 A circuit is enough.

Cable and protective device

CircuitTypical cableTypical use
32 A6 mm² twin and earthMost cookers and hob plus oven combinations
40 A or more10 mm² twin and earthLarge range cookers and long runs

These are typical choices. The designer confirms the size from the route, installation method and length.

The cooker switch

A double-pole cooker control switch isolates the appliance. It should be within 2 m of the cooker so it can be reached quickly, but not directly above the hob where you would have to reach over hot pans. One switch can serve a separate hob and oven if both are within 2 m of it.

Check the rules. Induction hobs and some ovens come with specific circuit requirements. The manufacturer's instructions take priority over rules of thumb.

Hob and oven on one circuit?

Often, yes. A built-in oven and a separate hob can share one cooker circuit when the combined load, after diversity, is within the circuit rating and each appliance is connected with suitably rated cable. Some single ovens are fitted with a plug and run from a socket instead.

Drawing it

On the plan, the cooker circuit is one clean line: consumer unit, route, cooker control unit, appliance. Give it its own colour so it cannot be confused with the socket ring, and label it with the cable size and the protective device. In RoomPlot the route length is totalled for you, ready for the materials list.

Frequently asked questions

Does a cooker need its own circuit?

A freestanding electric cooker or a hardwired hob does. A small single oven rated under about 3 kW may be supplied with a plug for an ordinary socket: check its instructions.

Can I use 4 mm² cable for a cooker?

Sometimes, for small loads on short runs, but 6 mm² is the common choice because it covers most appliances and future replacements.

How high should the cooker switch be?

There is no single required height in BS 7671. It is usually fitted above the worktop to one side of the cooker, where it is easy to see and reach.

Free lesson. Want the full picture? Kitchens and bathrooms is part of our free electrical floor plans course, with interactive exercises.

Sources

Plan it on your phone. Lay out the kitchen circuits in their own colours and get the cable lengths without a tape measure. Download RoomPlot on the App Store and draw your first electrical plan in minutes, or see what it does on our electricians page.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Downlight Spacing Guide: How Many Downlights Does a Room Need? Work out how many downlights a room needs and how far apart to space them: the lumen method, a simple spacing rule, a worked example and common mistakes. 4 min read