Lesson 7 of 18 All lessons
- 1What an electrical floor plan is, and who uses it
- 2Electrical symbols: lights, switches, sockets and distribution
- 3Circuits explained: lighting, rings, radials and dedicated supplies
- 4Drawing the base plan: measuring, doors and fixed fittings
- 5Lighting and switching: one-way, two-way and intermediate
- 6Sockets and spurs: how many, where, and on which circuit
- 7Kitchens and bathrooms: special rules for special rooms
- 8Cable routes, lengths and circuit schedules
- 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
- 10UK rules: BS 7671, Part P and what applies where
- 11UK protection: consumer units, RCD types and surge protection
- 12UK earthing systems, mounting heights and certificates
- 13US rules: the NEC, receptacle spacing, GFCI and AFCI
- 14US kitchens and bathrooms: receptacle rules on the plan
- 15US panels, GFCI, AFCI and wire sizes
- 16Worked example: from survey to a finished plan
- 17Checking your plan and handing it over
- 18Final test: check what you have learned
In this lesson
- Kitchens usually get their own socket circuit plus a dedicated cooker circuit.
- Bathroom zones: zone 1 over the bath or tray, zone 2 extending 0.6 m beyond.
- Sockets other than SELV and shaver units stay well away from zone 1.
Kitchens carry the biggest loads in a home and bathrooms are special locations with their own section of the wiring rules. This lesson covers both.
Kitchens
- A dedicated socket circuit for the worktops.
- A cooker circuit to a cooker control unit beside the hob, never directly above it.
- Fused spurs above the worktop to isolate integrated appliances.
- Lighting over the work surfaces, not only in the middle of the ceiling.
Bathrooms (UK, BS 7671 Section 701)
- Zone 0: inside the bath or tray, IPX7, SELV only.
- Zone 1: above the bath or tray up to 2.25 m, IPX4 minimum (IPX5 for water jets).
- Zone 2: 0.6 m beyond zone 1, IPX4 minimum.
- Sockets other than SELV and shaver units are kept 2.5 m from the zone 1 boundary under the amended 2018 edition.
- Circuits serving the room need 30 mA RCD protection.
In the US, bathroom receptacles need GFCI protection and a dedicated 20 A circuit is typically required; check the adopted NEC edition.
Try it
Draw your bathroom with the bath or shower, then mark zone 1 and zone 2. Is every light and fan rated for its zone?
Check your understanding
Official documents and further reading
Next lesson 8Cable routes, lengths and circuit schedules
Progress is saved in this browser.