Module 2 · Designing a layout · Lesson 7 of 18

Kitchens and bathrooms: special rules for special rooms

Free lesson: plan kitchen circuits, cooker controls and appliance spurs, and draw bathroom zones with the right IP ratings.

9 min · 0 XP · 0 of 18 lessons done

Lesson 7 of 18 All lessons
  1. 1What an electrical floor plan is, and who uses it
  2. 2Electrical symbols: lights, switches, sockets and distribution
  3. 3Circuits explained: lighting, rings, radials and dedicated supplies
  4. 4Drawing the base plan: measuring, doors and fixed fittings
  5. 5Lighting and switching: one-way, two-way and intermediate
  6. 6Sockets and spurs: how many, where, and on which circuit
  7. 7Kitchens and bathrooms: special rules for special rooms
  8. 8Cable routes, lengths and circuit schedules
  9. 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
  10. 10UK rules: BS 7671, Part P and what applies where
  11. 11UK protection: consumer units, RCD types and surge protection
  12. 12UK earthing systems, mounting heights and certificates
  13. 13US rules: the NEC, receptacle spacing, GFCI and AFCI
  14. 14US kitchens and bathrooms: receptacle rules on the plan
  15. 15US panels, GFCI, AFCI and wire sizes
  16. 16Worked example: from survey to a finished plan
  17. 17Checking your plan and handing it over
  18. 18Final test: check what you have learned

In this lesson

  • Kitchens usually get their own socket circuit plus a dedicated cooker circuit.
  • Bathroom zones: zone 1 over the bath or tray, zone 2 extending 0.6 m beyond.
  • Sockets other than SELV and shaver units stay well away from zone 1.

Kitchens carry the biggest loads in a home and bathrooms are special locations with their own section of the wiring rules. This lesson covers both.

Kitchens

USB C1 C2 C4 Kitchen Kitchen electrical plan Ring, cooker circuit and lighting CIRCUITS (CABLE ROUTES) C1 Lighting 1.5 mm² · 6 A RCBO C2 Kitchen ring 2.5 mm² · 32 A RCBO C4 Cooker 6 mm² · 32 A RCBO Connection (switch to light) SYMBOLS Surface ceiling light One-way switch Double socket Fused spur Cooker Control Unit Consumer Unit
A kitchen with its own ring (blue), a dedicated cooker circuit (purple) to a control unit, and lighting.
  • A dedicated socket circuit for the worktops.
  • A cooker circuit to a cooker control unit beside the hob, never directly above it.
  • Fused spurs above the worktop to isolate integrated appliances.
  • Lighting over the work surfaces, not only in the middle of the ceiling.

Bathrooms (UK, BS 7671 Section 701)

PLAN VIEW · ZONES 1 AND 2 RUN TO 2.25 M ABOVE THE FLOORHALL ZONE 1ZONE 2ZONE 1ZONE 2OUTSIDE ZONES Bathroom zones Plan view, BS 7671 Section 701 Zone 1: bath and shower tray IPX4 minimum, IPX5 for water jets Zone 2: 0.6 m beyond zone 1 IPX4 minimum Recessed ceiling light Rated for the zone it sits in Extractor fan Isolated from outside the room One-way switch Outside the room, or a pull cord Fused spur (fan isolator) In the hall, outside the zones Lighting cable route
Bathroom zones in plan view: zone 1 over the bath and tray, zone 2 extending 0.6 m beyond.
  • Zone 0: inside the bath or tray, IPX7, SELV only.
  • Zone 1: above the bath or tray up to 2.25 m, IPX4 minimum (IPX5 for water jets).
  • Zone 2: 0.6 m beyond zone 1, IPX4 minimum.
  • Sockets other than SELV and shaver units are kept 2.5 m from the zone 1 boundary under the amended 2018 edition.
  • Circuits serving the room need 30 mA RCD protection.

In the US, bathroom receptacles need GFCI protection and a dedicated 20 A circuit is typically required; check the adopted NEC edition.

Try it

Draw your bathroom with the bath or shower, then mark zone 1 and zone 2. Is every light and fan rated for its zone?

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Kitchen Electrical Plan: Sockets, Spurs and the Cooker Circuit Plan kitchen electrics on a floor plan: worktop sockets, fused spurs for appliances, a dedicated cooker circuit with a control unit, and kitchen lighting. 3 min read Electricians Bathroom Electrical Zones on a Floor Plan (BS 7671 Section 701) Draw bathroom electrical zones on a floor plan: zone 0, 1 and 2, IP ratings, socket distances, shaver units and where switches and isolators go. 4 min read Electricians Kitchen Extension Electrical Plan: Step by Step Plan the electrics for a kitchen extension: a new ring, cooker circuit, island power, pendants and dimmable downlights, joined to the existing house. 3 min read