UK protection: consumer units, RCD types and surge protection

Free lesson for the UK: what goes inside a modern consumer unit, how RCBOs, RCD types and surge protection work, and how to match each device to its circuit.

9 min · 0 XP · 0 of 18 lessons done

Lesson 11 of 18 All lessons
  1. 1What an electrical floor plan is, and who uses it
  2. 2Electrical symbols: lights, switches, sockets and distribution
  3. 3Circuits explained: lighting, rings, radials and dedicated supplies
  4. 4Drawing the base plan: measuring, doors and fixed fittings
  5. 5Lighting and switching: one-way, two-way and intermediate
  6. 6Sockets and spurs: how many, where, and on which circuit
  7. 7Kitchens and bathrooms: special rules for special rooms
  8. 8Cable routes, lengths and circuit schedules
  9. 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
  10. 10UK rules: BS 7671, Part P and what applies where
  11. 11UK protection: consumer units, RCD types and surge protection
  12. 12UK earthing systems, mounting heights and certificates
  13. 13US rules: the NEC, receptacle spacing, GFCI and AFCI
  14. 14US kitchens and bathrooms: receptacle rules on the plan
  15. 15US panels, GFCI, AFCI and wire sizes
  16. 16Worked example: from survey to a finished plan
  17. 17Checking your plan and handing it over
  18. 18Final test: check what you have learned

In this lesson

  • A modern consumer unit has a main switch, an SPD and an RCBO for each circuit.
  • Type A RCDs are the usual choice for general domestic circuits. Type AC is now limited.
  • The device rating follows the circuit: 6 A lighting, 32 A rings and cookers, larger for showers.

The consumer unit is the heart of a UK installation. Every circuit on your plan lands on one of its ways, and each way has a protective device chosen for that circuit. This lesson opens the cover.

CONSUMER UNIT UPGRADEOld fuse board vs a modern consumer unit OLD BOARD Rewirable fuses or old breakers No RCD protection, or one RCD for everything No surge protection Plastic or wooden enclosure Faded or missing circuit labels MODERN CONSUMER UNIT One RCBO per circuit, so a fault trips only that circuit 30 mA RCD protection where it is required Surge protection device at the origin Non-combustible enclosure A clear circuit schedule that matches the plan
An old fuse board compared with a modern consumer unit.

Inside a modern consumer unit

  • Main switch: isolates everything.
  • Surge protection device (SPD): diverts voltage spikes to earth.
  • RCBOs: one per circuit, combining overcurrent protection with a 30 mA RCD.
  • A non-combustible enclosure, in practice steel.

Some boards use two shared RCDs with ordinary circuit breakers instead. They cost less, but one earth fault switches off half the house.

RCD types

RCD TYPESWhich RCD type detects what TYPE DETECTS TYPICAL USE AC Alternating residual current only Older installations. Now limited to loads with no DC components A AC plus pulsating DC The usual choice for general domestic circuits F Type A plus mixed frequencies Single-phase inverter loads: some washing machines, air conditioning, heat pumps B Type F plus smooth DC Three-phase drives, some EV charging and solar or battery inverters Always follow the equipment manufacturer's instructions when choosing the RCD type.
RCD types. Each one detects everything the type above it does, plus more.

The letter says which shapes of fault current the device can see. Type AC is being phased out of general use because modern electronics can blind it. Type A is the everyday choice. Inverter loads and EV charging can need Type F or B, or extra DC detection: the manufacturer's instructions decide.

Surge protection

SURGE PROTECTIONThe three SPD types and where they go TYPE WHERE IT IS FITTED WHAT IT HANDLES Type 1 At the origin, for buildings with a lightning protection system or an overhead supply Partial lightning current Type 2 In the consumer unit. The usual choice for homes Switching surges and indirect lightning Type 3 Close to sensitive equipment, with a Type 2 upstream Fine protection for electronics BS 7671 Section 443 decides when surge protection is required. Many installers now fit a Type 2 SPD as standard.
The three SPD types. Most homes use a Type 2 device in the consumer unit.

Since Amendment 2 of BS 7671, surge protection is expected in most new work. The owner of a single home can decline it after the risk is explained, and that should be recorded.

Arc fault detection

AFDDs detect dangerous arcing in damaged cables and loose connections. BS 7671 requires them for socket circuits in some higher-risk residential buildings and recommends them elsewhere.

On the plan

Next to the consumer unit symbol, write the circuit list: number, name, device and cable, such as "C2 Kitchen ring, B32 RCBO, 2.5 mm²". Use the same names on the board labels.

This is a summary. Check the current edition of BS 7671 before you design, and remember that replacing a consumer unit is notifiable work in England and Wales.

Free calculators for this lesson: Zs calculator, UK cable size calculator.

Try it

Open the cover flap of your own consumer unit, without removing anything, and read the labels. Can you tell which circuit feeds each room? If not, that is a job for a plan.

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians RCD Types Explained: AC, A, F and B, and Which One a Circuit Needs RCD types AC, A, F and B explained in plain English: what each detects, why Type AC is being phased out in UK homes and how to note the type on a plan. 3 min read Electricians Surge Protection Devices (SPDs): Does a UK Home Need One? Surge protection in UK homes explained: what an SPD does, the three types, what BS 7671 Section 443 expects since Amendment 2 and where the device goes. 3 min read