Lesson 11 of 18 All lessons
- 1What an electrical floor plan is, and who uses it
- 2Electrical symbols: lights, switches, sockets and distribution
- 3Circuits explained: lighting, rings, radials and dedicated supplies
- 4Drawing the base plan: measuring, doors and fixed fittings
- 5Lighting and switching: one-way, two-way and intermediate
- 6Sockets and spurs: how many, where, and on which circuit
- 7Kitchens and bathrooms: special rules for special rooms
- 8Cable routes, lengths and circuit schedules
- 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
- 10UK rules: BS 7671, Part P and what applies where
- 11UK protection: consumer units, RCD types and surge protection
- 12UK earthing systems, mounting heights and certificates
- 13US rules: the NEC, receptacle spacing, GFCI and AFCI
- 14US kitchens and bathrooms: receptacle rules on the plan
- 15US panels, GFCI, AFCI and wire sizes
- 16Worked example: from survey to a finished plan
- 17Checking your plan and handing it over
- 18Final test: check what you have learned
In this lesson
- A modern consumer unit has a main switch, an SPD and an RCBO for each circuit.
- Type A RCDs are the usual choice for general domestic circuits. Type AC is now limited.
- The device rating follows the circuit: 6 A lighting, 32 A rings and cookers, larger for showers.
The consumer unit is the heart of a UK installation. Every circuit on your plan lands on one of its ways, and each way has a protective device chosen for that circuit. This lesson opens the cover.
Inside a modern consumer unit
- Main switch: isolates everything.
- Surge protection device (SPD): diverts voltage spikes to earth.
- RCBOs: one per circuit, combining overcurrent protection with a 30 mA RCD.
- A non-combustible enclosure, in practice steel.
Some boards use two shared RCDs with ordinary circuit breakers instead. They cost less, but one earth fault switches off half the house.
RCD types
The letter says which shapes of fault current the device can see. Type AC is being phased out of general use because modern electronics can blind it. Type A is the everyday choice. Inverter loads and EV charging can need Type F or B, or extra DC detection: the manufacturer's instructions decide.
Surge protection
Since Amendment 2 of BS 7671, surge protection is expected in most new work. The owner of a single home can decline it after the risk is explained, and that should be recorded.
Arc fault detection
AFDDs detect dangerous arcing in damaged cables and loose connections. BS 7671 requires them for socket circuits in some higher-risk residential buildings and recommends them elsewhere.
On the plan
Next to the consumer unit symbol, write the circuit list: number, name, device and cable, such as "C2 Kitchen ring, B32 RCBO, 2.5 mm²". Use the same names on the board labels.
This is a summary. Check the current edition of BS 7671 before you design, and remember that replacing a consumer unit is notifiable work in England and Wales.
Free calculators for this lesson: Zs calculator, UK cable size calculator.
Try it
Open the cover flap of your own consumer unit, without removing anything, and read the labels. Can you tell which circuit feeds each room? If not, that is a job for a plan.