A surge protection device, or SPD, sits in the consumer unit and diverts short, sharp voltage spikes to earth before they reach your equipment. They used to be rare in homes. Since 2022 they have become a standard part of most new installations and consumer unit changes. Here is why, and what to ask for.
Key takeaways
- An SPD protects equipment from transient overvoltages caused by lightning and switching events.
- Since Amendment 2 of BS 7671, surge protection is expected in most new work unless the owner of a home declines it.
- A Type 2 SPD in the consumer unit is the usual domestic solution.
- The connecting leads must be kept short, so the position in the board matters.
What is a surge?
A transient overvoltage is a spike lasting millionths of a second that can reach thousands of volts. Lightning striking the network nearby is the dramatic cause. Switching of large loads is the everyday one. Modern homes are full of electronics that these spikes can damage or wear out: boilers, LED drivers, chargers, appliances and smart controls.
What BS 7671 expects
Section 443 requires protection against transient overvoltages where the consequences could include serious injury or loss of life, failure of a safety service, or significant financial or data loss. For all other cases, protection is to be provided unless the owner declines it. In a single dwelling that means the homeowner can choose not to have an SPD, but only after the risk has been explained, and the decision should be recorded.
Check the rules. This is a summary, not the regulation. Check Section 443 in the current edition of BS 7671 before you design or quote.
The three types
- Type 1 handles partial lightning current. It is used at the origin where the building has a lightning protection system or an overhead supply.
- Type 2 handles switching surges and indirect lightning. It sits in the consumer unit and is the usual choice for homes.
- Type 3 gives fine protection close to sensitive equipment and is only used with a Type 2 upstream.
Combined Type 1 and 2 devices are common where an overhead line feeds the property.
Where it goes
The SPD is connected at the origin of the installation, as close to the incoming supply as practical, with its own overcurrent protection if the manufacturer requires it. The connecting leads should be as short and straight as possible, because every extra centimetre reduces the protection. Many consumer units now ship with the SPD fitted next to the main switch for exactly this reason.
On the plan and in the quote
Mark the SPD beside the consumer unit on the plan and list it in the quote as its own line. If a client declines it, note that on the certificate. A short text label on the RoomPlot plan, exported with the legend, keeps the decision with the drawing.
Frequently asked questions
Is surge protection a legal requirement in UK homes?
BS 7671 is not law in itself, but it is the standard that compliant work follows. It expects surge protection in most new work, with the owner of a single dwelling able to decline it.
Does an SPD need replacing?
Yes, eventually. SPDs wear with each surge they absorb. Most have a status window that changes colour when the device or its cartridge needs replacing.
Will an SPD protect against a direct lightning strike?
A Type 2 device is not designed for a direct strike on the building. Buildings with a lightning protection system need Type 1 devices and a coordinated design.