Zs Calculator (Earth Fault Loop)

Estimate the earth fault loop impedance of a radial circuit at the design stage and see whether the breaker will trip in time.

Calculator
Cable, line / earth
Breaker type
Breaker rating

Fill in the fields above to see results.

How it works

Zs = Ze + (R1 + R2). R1 + R2 comes from the resistance per metre of the line and protective conductors at 20 degC, multiplied by 1.2 to allow for the conductors warming up in use. The maximum Zs is 0.95 x 230 V divided by the current that trips the breaker instantly: 5 x its rating for Type B, 10 x for Type C and 20 x for Type D. Measured values on site are normally compared with 80% of the maximum. This is a design estimate for a radial circuit and does not replace testing.

Frequently asked questions

What is a typical Ze?

Network operators quote maximum values of 0.35 ohm for TN-C-S (PME) supplies and 0.8 ohm for TN-S supplies. TT installations are much higher and rely on RCDs. Use the measured value where you have one.

Why is the measured Zs compared with 80% of the maximum?

The tabulated maximum is for conductors at their operating temperature. A test is done on cold cables, which have lower resistance, so the 80% rule of thumb allows for the rise when the circuit is loaded.