Electrical
Voltage Drop Calculator
Long runs lose voltage. Enter the current, the one-way length and the cable size to see the drop in volts and percent.
Fill in the fields above to see results.
How it works
For UK cable the drop is the tabulated mV/A/m figure x current x length / 1000, using the BS 7671 values for 70 degC flat twin and earth, checked against 5% for power and 3% for lighting. For US wire the drop is 2 x 12.9 x current x length in feet / circular mils, checked against the 3% the NEC recommends for a branch circuit. These are single-phase figures for copper conductors: always confirm against the current tables for the job.
Frequently asked questions
What voltage drop is allowed in the UK?
BS 7671 gives 3% for lighting circuits and 5% for other uses, measured from the origin of the installation: 6.9 V and 11.5 V on a 230 V supply.
What voltage drop does the NEC allow?
The NEC does not set a mandatory limit for ordinary branch circuits. Its informational notes recommend about 3% on a branch circuit and 5% for feeder and branch circuit combined.