Cable Size Calculator (UK)

Enter the current, how the cable is installed and how far it runs. The calculator finds the smallest twin and earth size that carries the load and stays inside the voltage drop limit.

Calculator
How is it installed?
Circuit

Fill in the fields above to see results.

How it works

Current ratings and mV/A/m voltage drop values are the tabulated figures for 70 degC thermoplastic flat twin and earth cable in BS 7671 Table 4D5. A cable buried in insulation carries far less than one clipped to a joist, which is why the installation method matters. No correction is applied for grouping or high ambient temperature, and the protective device still has to suit the cable: treat the answer as a starting point and confirm it against the current edition.

Frequently asked questions

What size cable do I need for a 32 A circuit?

Clipped direct, 4 mm² twin and earth carries 37 A, so it suits a 32 A radial. A ring final uses 2.5 mm² because the current has two paths. Cable run through thermal insulation needs a larger size.

Why does insulation reduce the current a cable can carry?

A cable sheds heat to its surroundings. Loft or wall insulation traps that heat, so the rating falls: 2.5 mm² twin and earth is 27 A clipped direct but 13.5 A when surrounded by insulation in a stud wall.