Lesson 14 of 18 All lessons
- 1What an electrical floor plan is, and who uses it
- 2Electrical symbols: lights, switches, sockets and distribution
- 3Circuits explained: lighting, rings, radials and dedicated supplies
- 4Drawing the base plan: measuring, doors and fixed fittings
- 5Lighting and switching: one-way, two-way and intermediate
- 6Sockets and spurs: how many, where, and on which circuit
- 7Kitchens and bathrooms: special rules for special rooms
- 8Cable routes, lengths and circuit schedules
- 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
- 10UK rules: BS 7671, Part P and what applies where
- 11UK protection: consumer units, RCD types and surge protection
- 12UK earthing systems, mounting heights and certificates
- 13US rules: the NEC, receptacle spacing, GFCI and AFCI
- 14US kitchens and bathrooms: receptacle rules on the plan
- 15US panels, GFCI, AFCI and wire sizes
- 16Worked example: from survey to a finished plan
- 17Checking your plan and handing it over
- 18Final test: check what you have learned
In this lesson
- Kitchen countertops: no point more than 24 in from a receptacle, on at least two 20 A circuits.
- Bathrooms: a GFCI receptacle within 3 ft of each basin, on a 20 A circuit.
- Recent editions keep receptacles out of a zone 3 ft from a tub or shower.
Kitchens and bathrooms have the tightest rules in the National Electrical Code. Both are easy to get right when you draw them first.
Kitchen countertops
- Every countertop space 12 in or wider needs a receptacle.
- No point along the wall line is more than 24 in from a receptacle in that space.
- A sink or range splits the counter into separate spaces.
- At least two 20 A small-appliance circuits serve the countertop receptacles.
- Kitchen receptacles need GFCI protection, and kitchen circuits need AFCI protection.
Island and peninsula rules have changed from edition to edition. Ask which edition your jurisdiction enforces.
Bathrooms
- A receptacle within 3 ft of the outside edge of each basin.
- At least one 20 A circuit for bathroom receptacles, with GFCI protection.
- Under the 2023 edition, no receptacles in a zone 3 ft out from and 8 ft above the tub rim or shower threshold.
- Hanging fixtures, track lighting and ceiling fans stay out of that zone too.
States and cities adopt different editions of the NEC, often with amendments. Treat this lesson as a map, and check the adopted edition for the job.
Free calculators for this lesson: receptacle spacing calculator.
Try it
Sketch your own kitchen counter. Mark a receptacle within 2 ft of each end of every run, then check that no gap between receptacles is more than 4 ft.