NEC Bathroom Electrical Requirements: Receptacles, Circuits and the Tub Zone

NEC bathroom rules explained: the receptacle within 3 ft of each basin, the 20 A bathroom circuit, GFCI protection and the 3 ft zone around a tub or shower.

4 min read · 21 November 2026 · RoomPlot Team

A bathroom is small, wet and full of appliances that draw a lot of current. The National Electrical Code deals with that using a handful of clear rules. Draw them on a plan once and every bathroom after that is quick.

GFCI3 ft Bathroom No receptacles within 3 ft of the tub 20 A circuit, to the panel Bathroom layout NEC rules that shape the plan 20 A bathroom circuit Feeds the basin receptacle Tub and shower zone 3 ft out and 8 ft up: no receptacles Connection (switch to light) SYMBOLS GFCI GFCI receptacle Light Exhaust fan Single-pole switch
A bathroom plan with the rules drawn on it: a GFCI receptacle beside the basin and a zone around the tub that stays clear of receptacles.

Key takeaways

  • Each basin needs a receptacle within 3 ft of its outside edge.
  • Bathroom receptacles are fed by at least one 20 A circuit and need GFCI protection.
  • Recent editions keep receptacles out of a zone 3 ft out from and 8 ft above a bathtub rim or shower threshold.
  • At least one wall-switch-controlled lighting outlet is required.

The receptacle by the basin

NEC 210.52(D) requires at least one receptacle within 3 ft of the outside edge of each basin. It goes on a wall or partition next to the basin, on the countertop, or on the side or face of the basin cabinet no more than 12 in below the top. One receptacle between two basins can serve both if it is within 3 ft of each.

The 20 A bathroom circuit

Under 210.11(C)(3), bathroom receptacles are supplied by at least one 120 V, 20 A branch circuit that has no other outlets. There is a useful exception: if the circuit supplies a single bathroom, it can also feed other equipment in that same bathroom, such as the light and fan, within the load limits.

GFCI protection

All bathroom receptacles need ground-fault circuit-interrupter protection under 210.8(A). A GFCI receptacle at the basin or a GFCI breaker in the panel both do the job.

The tub and shower zone

Receptacles may not be installed inside a tub or shower space. The 2023 edition widened this to a zone measured 3 ft horizontally from the bathtub rim or shower threshold and 8 ft vertically above it, with an exception for bathrooms too small to allow it. Luminaires in that zone have their own rules: no hanging or cord-connected fixtures, track lighting or ceiling fans, and fixtures there must be rated for damp or wet locations.

Check the rules. States and cities adopt different editions of the NEC, often with local amendments. This guide is a plain-English summary based on recent editions. Always check the edition your jurisdiction enforces and ask your inspector when in doubt.

Lighting and ventilation

The NEC requires at least one lighting outlet controlled by a wall switch in every bathroom. An exhaust fan is usually a building code requirement where there is no openable window. On the plan, show which switch controls the light and which controls the fan.

Drawing the bathroom

  1. Draw the room with the tub, toilet and basin to scale.
  2. Shade the 3 ft zone around the tub or shower.
  3. Place the receptacle beside the basin, outside the zone.
  4. Add the light, the fan and their switch by the door, and link each switch to what it controls.
  5. Draw the 20 A circuit back toward the panel.

RoomPlot has the symbols for each of these, red connection lines for switch control and coloured routes for the circuits, so the finished sheet shows the rules at a glance.

Frequently asked questions

Does a bathroom need its own circuit?

Bathroom receptacles need a 20 A circuit with no outlets outside bathrooms. If the circuit serves just one bathroom it can also supply that bathroom's lights and fan.

How far must an outlet be from a bathtub?

Under the 2023 NEC, receptacles stay out of a zone 3 ft horizontally from the tub rim or shower threshold. Earlier editions only prohibited receptacles within the tub or shower space itself.

Does a bathroom need AFCI protection?

Bathrooms are not in the NEC list of areas requiring AFCI protection, although some jurisdictions amend this.

Free lesson. Want the full picture? Kitchens and bathrooms is part of our free electrical floor plans course, with interactive exercises.

Sources

Plan it on your phone. Draw the tub zone, the basin receptacle and the switch connections on one clear bathroom plan. Download RoomPlot on the App Store and draw your first electrical plan in minutes, or see what it does on our electricians page.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read