US panels, GFCI, AFCI and wire sizes

Free lesson for the US: where GFCI and AFCI protection are required, the working space in front of a panel, and how wire size matches the breaker.

10 min · 0 XP · 0 of 18 lessons done

Lesson 15 of 18 All lessons
  1. 1What an electrical floor plan is, and who uses it
  2. 2Electrical symbols: lights, switches, sockets and distribution
  3. 3Circuits explained: lighting, rings, radials and dedicated supplies
  4. 4Drawing the base plan: measuring, doors and fixed fittings
  5. 5Lighting and switching: one-way, two-way and intermediate
  6. 6Sockets and spurs: how many, where, and on which circuit
  7. 7Kitchens and bathrooms: special rules for special rooms
  8. 8Cable routes, lengths and circuit schedules
  9. 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
  10. 10UK rules: BS 7671, Part P and what applies where
  11. 11UK protection: consumer units, RCD types and surge protection
  12. 12UK earthing systems, mounting heights and certificates
  13. 13US rules: the NEC, receptacle spacing, GFCI and AFCI
  14. 14US kitchens and bathrooms: receptacle rules on the plan
  15. 15US panels, GFCI, AFCI and wire sizes
  16. 16Worked example: from survey to a finished plan
  17. 17Checking your plan and handing it over
  18. 18Final test: check what you have learned

In this lesson

  • GFCI protects people from shock in wet and damp locations. AFCI protects against fire in living areas.
  • Keep a space 30 in wide, 36 in deep and 6 ft 6 in high clear in front of a home panel.
  • 14 AWG copper goes with 15 A, 12 AWG with 20 A and 10 AWG with 30 A.

This lesson covers the protection decisions on a US dwelling plan: which circuits need GFCI or AFCI, where the panel can go, and what wire size each breaker needs.

GFCI: where shock risk is highest

GFCI GFCI GFCI OUTDOORS: GFCI OUTDOORS: GFCIKitchen Bathroom Bedroom Garage Where GFCI is required NEC 210.8(A), dwelling units GFCI protection Kitchen, bathroom, garage, outdoors Also in the list Basements, laundry areas, crawl spaces, and within 6 ft of a sink, tub or shower
GFCI areas: kitchen, bathroom, garage and outdoors, plus basements, laundry areas and near sinks.

A ground-fault circuit interrupter trips when current leaks to ground. The NEC requires it for receptacles in bathrooms, kitchens, garages, outdoors, basements, crawl spaces and laundry areas, and within 6 ft of sinks, tubs and showers.

AFCI: where fire risk is highest

AFCI AFCI AFCI NOT IN THE AFCI LIST NOT IN THE AFCI LISTKitchen Bathroom Bedroom Garage Where AFCI is required NEC 210.12, dwelling units AFCI protection Kitchens, bedrooms, living areas, hallways, closets, laundry areas Not in the AFCI list Bathrooms, garages, outdoors
AFCI areas: kitchens, bedrooms, living areas, hallways, closets and laundry areas.

An arc-fault circuit interrupter detects arcing in damaged or loose wiring. It is required for 120 V, 15 A and 20 A circuits serving most living areas. Kitchens and laundry areas need both kinds of protection, which a dual-function breaker provides.

The panel

NEC 110.26Working space in front of a panel PLAN VIEW 30 in wide 36 in deep Keep clear ELEVATION 6 ft 6 in Clear height or the equipment height, if taller Depth comes from Table 110.26(A)(1): 36 in is the usual figure for a 120/240 V home panel.
Working space in front of a panel: 30 in wide, 36 in deep, 6 ft 6 in high.

Draw the working space on the plan as a rectangle in front of the panel and keep it clear. Panels cannot go in bathrooms or clothes closets.

Wire sizes

QUICK REFERENCEBreaker and copper wire size BREAKER COPPER WIRE TYPICAL CIRCUITS 15 A 14 AWG Lighting, general receptacles 20 A 12 AWG Kitchen, bathroom, laundry and garage receptacles 30 A 10 AWG Electric dryer, water heater 40 A 8 AWG Electric range, a 32 A EV charger 50 A 6 AWG Electric range, a 40 A EV charger 60 A 6 AWG in conduit, or 4 AWG cable A 48 A hardwired EV charger Typical sizes for copper conductors. Check ampacity tables, terminal ratings, cable type and voltage drop for the job.
Typical copper wire sizes for common residential breakers.

The breaker protects the wire, so the wire must be large enough for the breaker. Long runs may need a larger size to limit voltage drop, and the length comes from your plan.

States and cities adopt different editions of the NEC, often with amendments. Confirm the adopted edition and ask the inspector when in doubt.

Free calculators for this lesson: conduit fill calculator, box fill calculator, voltage drop calculator.

Try it

Walk through your home and list every receptacle that should be GFCI protected. Press the test button on one and check that it resets.

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians GFCI Requirements by Room: Where the NEC Requires Ground-Fault Protection Where GFCI protection is required in a US home, room by room: kitchens, bathrooms, garages, outdoors, basements and laundry areas, shown on a floor plan. 3 min read Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Electrical Panel Clearance Requirements: The Working Space Rules in NEC 110.26 NEC 110.26 working space for a home electrical panel: 30 in wide, 36 in deep and 6 ft 6 in high, where panels cannot go and how to show it on a plan. 3 min read