Conduit Fill Calculator
Pick the conduit and the wire, enter how many conductors, and see the fill percentage against the NEC limit.
Fill in the fields above to see results.
How it works
NEC Chapter 9 Table 1 limits the cross-section of a conduit that conductors may fill: 53% for one conductor, 31% for two and 40% for three or more. This calculator uses the Table 4 internal areas for EMT and the Table 5 areas for THHN/THWN-2 conductors, all of one size. Mixed sizes, other conduit types and derating for more than three current-carrying conductors are separate checks.
Frequently asked questions
How many 12 AWG wires fit in 1/2 in EMT?
Nine THHN conductors. The 40% fill area of 1/2 in EMT is 0.122 sq in, and each 12 AWG THHN conductor is 0.0133 sq in.
Why is the limit lower for two wires than for three?
Two conductors can lie side by side and jam across the conduit, so the limit for exactly two is 31%. Three or more settle into the 40% allowance.