Electrical

Box Fill Calculator

Count what goes in the box. The calculator adds up the volume allowances and tells you the smallest common box that fits.

Calculator
Wire size
Internal cable clamps

Fill in the fields above to see results.

How it works

NEC 314.16(B) gives each item a volume allowance based on the wire size: 2.00 cu in for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG, 3.00 for 8 AWG and 5.00 for 6 AWG. Each insulated conductor counts once, each device yoke counts twice, internal clamps count once in total and up to four equipment grounding conductors count once, with a quarter allowance for each one beyond four. This tool assumes all conductors are one size: with mixed sizes, each item uses its own conductor size.

Frequently asked questions

How many 12 AWG wires fit in an 18 cubic inch box?

18 / 2.25 = 8 allowances. A receptacle uses two and the grounds use one, which leaves five for insulated conductors if there are no internal clamps.

Do pigtails count?

No. A conductor that starts and ends inside the box, such as a pigtail, is not counted.