Module 1 · Foundations · Lesson 3 of 18

Circuits explained: lighting, rings, radials and dedicated supplies

Free lesson: how domestic circuits are organised, from lighting radials and ring finals to cooker and EV circuits, and how protective devices fit in.

8 min · 0 XP · 0 of 18 lessons done

Lesson 3 of 18 All lessons
  1. 1What an electrical floor plan is, and who uses it
  2. 2Electrical symbols: lights, switches, sockets and distribution
  3. 3Circuits explained: lighting, rings, radials and dedicated supplies
  4. 4Drawing the base plan: measuring, doors and fixed fittings
  5. 5Lighting and switching: one-way, two-way and intermediate
  6. 6Sockets and spurs: how many, where, and on which circuit
  7. 7Kitchens and bathrooms: special rules for special rooms
  8. 8Cable routes, lengths and circuit schedules
  9. 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
  10. 10UK rules: BS 7671, Part P and what applies where
  11. 11UK protection: consumer units, RCD types and surge protection
  12. 12UK earthing systems, mounting heights and certificates
  13. 13US rules: the NEC, receptacle spacing, GFCI and AFCI
  14. 14US kitchens and bathrooms: receptacle rules on the plan
  15. 15US panels, GFCI, AFCI and wire sizes
  16. 16Worked example: from survey to a finished plan
  17. 17Checking your plan and handing it over
  18. 18Final test: check what you have learned

In this lesson

  • Lighting usually runs as radials; UK sockets often as ring finals.
  • Big loads such as cookers, showers, heat pumps and EV chargers get dedicated circuits.
  • Every circuit starts at a protective device in the consumer unit or panel.

Before you place a single symbol, it helps to know how a home's electrics are organised. Every point belongs to a circuit, and every circuit starts at a protective device.

Consumer unit One RCBO per circuit, each way labelled to match the plan Main switch 100 A DP SPD Type 2 C1 B6 RCBO 30 mA 1.5 mm² Lighting C2 B32 RCBO 30 mA 2.5 mm² Kitchen ring C3 B32 RCBO 30 mA 2.5 mm² Sockets ring C4 B32 RCBO 30 mA 6 mm² Cooker C5 B20 RCBO 30 mA 2.5 mm² Garage radial C6 B32 RCBO 30 mA 6 mm² EV charger Ratings shown are typical for this sample house. Confirm each one against the design, cable length and installation method.
A consumer unit with a main switch, surge protection and one RCBO per circuit, colour coded to match the plan.

The main circuit types

  • Lighting radials: one cable runs out from the board to each light in turn, commonly on a 6 A device in the UK.
  • Ring finals (UK): a loop of 2.5 mm² cable that leaves the board, visits every socket and returns, on a 32 A device, typically serving up to about 100 m².
  • Radials for sockets: a single run, such as 2.5 mm² on 20 A for a smaller area. US homes use radial branch circuits throughout, commonly on 15 A or 20 A breakers.
  • Dedicated circuits: one circuit for one large load, such as a cooker, shower, heat pump or EV charger.

Protective devices

Circuit breakers protect against overload and short circuit. RCDs protect people by detecting current leaking to earth, and UK socket circuits up to 32 A generally need 30 mA RCD protection. An RCBO combines both in one device, so a fault only trips its own circuit. In the US, GFCI and AFCI protection play similar roles for specific locations.

Conductor colours

UK: brown line, blue neutral, green-and-yellow protective conductor. US: black or red hot, white neutral, green or bare ground. On the plan, colours identify circuits, not conductors.

Try it

Look at the labels in your own consumer unit or panel and write down every circuit. Which ones are lighting, which are sockets and which are dedicated?

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Ring Final Circuit on a Floor Plan: How to Draw and Check It Draw a ring final circuit on a floor plan: 2.5 mm² on 32 A, the 100 m² guide, spurs, radial alternatives, RCD and AFDD protection, shown clearly. 4 min read Electricians Consumer Unit Circuit Schedule: Match the Board to the Plan Write a consumer unit circuit schedule that matches the electrical floor plan: one row per way, ratings, cable sizes and what each circuit feeds. 3 min read Electricians How Many Sockets Can You Have on a Ring Main? How many sockets can go on a ring main: the 100 m² floor area guide, spurs, fused spurs and when to add a second ring, explained simply. 3 min read