Module 4 · US rules · Lesson 13 of 18

US rules: the NEC, receptacle spacing, GFCI and AFCI

Free lesson: US rules behind electrical plans: the NEC and local adoption, the 6 ft receptacle rule, GFCI and AFCI, and 2026 changes.

10 min · 0 XP · 0 of 18 lessons done

Lesson 13 of 18 All lessons
  1. 1What an electrical floor plan is, and who uses it
  2. 2Electrical symbols: lights, switches, sockets and distribution
  3. 3Circuits explained: lighting, rings, radials and dedicated supplies
  4. 4Drawing the base plan: measuring, doors and fixed fittings
  5. 5Lighting and switching: one-way, two-way and intermediate
  6. 6Sockets and spurs: how many, where, and on which circuit
  7. 7Kitchens and bathrooms: special rules for special rooms
  8. 8Cable routes, lengths and circuit schedules
  9. 9Dedicated circuits: showers, cookers, EV chargers and outbuildings
  10. 10UK rules: BS 7671, Part P and what applies where
  11. 11UK protection: consumer units, RCD types and surge protection
  12. 12UK earthing systems, mounting heights and certificates
  13. 13US rules: the NEC, receptacle spacing, GFCI and AFCI
  14. 14US kitchens and bathrooms: receptacle rules on the plan
  15. 15US panels, GFCI, AFCI and wire sizes
  16. 16Worked example: from survey to a finished plan
  17. 17Checking your plan and handing it over
  18. 18Final test: check what you have learned

In this lesson

  • The NEC (NFPA 70) is adopted, and often amended, state by state.
  • No point along a wall's floor line more than 6 ft from a receptacle.
  • GFCI and AFCI requirements shape where and how circuits are protected.

In the US, electrical plans follow the National Electrical Code, NFPA 70, as adopted by the state or city where you work. This lesson covers the rules that shape a dwelling plan.

Add one here 11 ft (max 12 ft) 6 ft Living room20 ft x 14 ft NEC 210.52(A) Measured along the floor line Duplex receptacle Within 6 ft Gap over 6 ft Doorway, not wall space Confirm the edition yourjurisdiction has adopted.
A living room checked against NEC 210.52(A): green within 6 ft of a receptacle, red a gap that needs one more.

The NEC and local adoption

The NEC is updated every three years; the current edition is 2026. States and cities adopt editions on their own schedules and often amend them, so always confirm what applies locally. NFPA offers free, read-only online access.

Receptacle spacing

In habitable rooms, no point along the floor line of any wall space may be more than 6 ft from a receptacle. Walls 2 ft or wider count; doorways break the wall space. Kitchen countertops have their own, tighter rule.

Protection

  • GFCI (210.8): kitchens, bathrooms, garages, outdoors, basements, laundry areas and more.
  • AFCI (210.12): most living spaces in a dwelling.
  • Dedicated circuits: kitchen small-appliance circuits, bathroom and laundry circuits are typical.

What changed in 2026

NEC 2026Changes that show up on a dwelling plan TOPIC WHAT CHANGED Wall space, 210.52(A) Fixed cabinets no longer count as wall space, with or without a countertop Below countertops No receptacles in the 24 in below a countertop, except in a drawer AFCI, 210.12 Retrofit AFCI devices allowed at the first receptacle or switch Surge protection Feeder surge protection extended to areas similar to bedrooms Emergency disconnect Service disconnect can serve as the emergency disconnect for one- and two-family homes GFCI for HVAC Class C GFCI permitted for listed HVAC equipment after 1 Sept 2026 Based on published summaries of the 2026 NEC. Adoption and local amendments vary by state.
Changes in the 2026 NEC that show up on a dwelling plan.

Try it

Measure one wall in a room at home. How many receptacles does it need so no point is more than 6 ft from one?

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians NEC Receptacle Spacing on a Floor Plan: The 6 ft and 12 ft Rule Check NEC 210.52 receptacle spacing on a floor plan: the 6 ft rule along the floor line, what counts as wall space, doorways, and 2026 changes. 3 min read Electricians 2026 NEC Changes for Homes: What Shows Up on the Plan The 2026 NEC changes that show up on a dwelling plan: wall space and cabinets, receptacles below countertops, AFCI retrofits and surge protection. 3 min read Electricians GFCI Requirements by Room: Where the NEC Requires Ground-Fault Protection Where GFCI protection is required in a US home, room by room: kitchens, bathrooms, garages, outdoors, basements and laundry areas, shown on a floor plan. 3 min read