NEC Receptacle Spacing on a Floor Plan: The 6 ft and 12 ft Rule

Check NEC 210.52 receptacle spacing on a floor plan: the 6 ft rule along the floor line, what counts as wall space, doorways, and 2026 changes.

3 min read · 20 November 2026 · RoomPlot Team

In US dwellings, receptacle placement is not a matter of taste. NEC 210.52 sets out where receptacle outlets are required, and the spacing rule for general wall space is one of the most checked items at rough-in inspection. Drawing the rule on a floor plan shows at a glance whether a room passes.

The rule in one sentence

In habitable rooms, receptacles have to be placed so that no point along the floor line of any wall space is more than 6 ft from a receptacle outlet. In practice that means receptacles no more than 12 ft apart along the wall, and one within 6 ft of each doorway.

Add one here 11 ft (max 12 ft) 6 ft Living room20 ft x 14 ft NEC 210.52(A) Measured along the floor line Duplex receptacle Within 6 ft Gap over 6 ft Doorway, not wall space Confirm the edition yourjurisdiction has adopted.
A living room checked against NEC 210.52(A): green shows wall space within 6 ft of a duplex receptacle, red marks a gap that needs one more receptacle, and doorways break the wall space.

Key takeaways

  • No point along a wall's floor line may be more than 6 ft from a receptacle.
  • That puts receptacles no more than 12 ft apart, with one within 6 ft of each doorway.
  • Any wall space 2 ft or wider counts.
  • Kitchen countertops follow a separate, tighter rule.

What counts as wall space

  • Any wall at least 2 ft wide counts, including wall measured around a corner.
  • Doorways, fireplaces and similar openings break the wall space.
  • Fixed glass panels in exterior walls count as wall space; sliding panels do not.
  • Under the 2026 edition, fixed cabinets are excluded from wall space whether or not they have a countertop.

Other dwelling rules that shape the plan

  • Kitchen countertops have their own, tighter spacing rule under 210.52(C).
  • GFCI protection under 210.8 covers kitchens, bathrooms, garages, outdoors, basements, laundry areas and more, and the list has grown in recent editions.
  • AFCI protection under 210.12 covers most living spaces in a dwelling.
  • The 2026 edition also restricts receptacles in the space up to 24 in below a countertop.

Check the standard. States and cities adopt NEC editions on their own schedules, and some amend them. Confirm which edition and local amendments apply before you lay out a job.

Common mistakes

  • Measuring across the room. The 6 ft rule is measured along the floor line of the wall, not diagonally.
  • Forgetting short walls. A 2 ft wall between two doors still counts as wall space.
  • Counting a switched receptacle as a required outlet without checking how your adopted edition treats it.
  • Using an old edition. Check which edition your jurisdiction has adopted before rough-in.

Checking spacing in RoomPlot

Switch the Electrical library to US, draw or scan the room and place duplex receptacles on the walls. Use the measure and dimension tools to check the distance between receptacles along each wall, and mark doorways as openings so they break the wall space. Exported plans can be shared as a PDF for the inspector or as a DXF for the designer. See more on our electricians page.

Frequently asked questions

How far apart should outlets be in a house?

In habitable rooms, no more than 12 ft apart along the wall, so that no point is more than 6 ft from one.

Does a hallway need a receptacle?

A hallway 10 ft or longer needs at least one receptacle.

Do receptacles behind furniture count?

Yes. The rule is measured along the wall, wherever the furniture ends up.

Free lesson. Want the full picture? US rules for electrical plans is part of our free electrical floor plans course, with interactive exercises.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read