Not all RCDs are the same. The letters AC, A, F and B describe which kinds of fault current the device can detect, and choosing the wrong one can leave a circuit with protection that does not operate when it should. Here is the difference, without the jargon.
Key takeaways
- An RCD trips when current leaks to earth. The type letter says which shapes of leakage current it can see.
- Type AC only detects plain alternating current and is now limited to loads with no DC components.
- Type A is the usual choice for general circuits in UK homes.
- Inverter-driven and DC-producing equipment may need Type F or Type B: check the manufacturer's instructions.
What an RCD does
A residual current device compares the current going out on the line conductor with the current coming back on the neutral. If some is missing, it is leaking to earth, possibly through a person. A 30 mA RCD disconnects quickly enough to prevent most fatal shocks. An RCBO is the same protection combined with a circuit breaker in one device.
The four types
Type AC
Detects alternating residual current only. Modern appliances full of electronics can put DC components into a fault current, and that can stop a Type AC device from tripping. Since Amendment 2 of BS 7671, Type AC is only for fixed equipment where the load is known to contain no DC components.
Type A
Detects alternating and pulsating DC residual currents. This covers most household equipment and is the general-purpose choice for domestic circuits.
Type F
Everything Type A does, plus mixed-frequency residual currents from single-phase inverter drives, found in some washing machines, air conditioning units and heat pumps.
Type B
Everything Type F does, plus smooth DC. Used with three-phase drives and some electric vehicle charging, solar and battery equipment.
Check the rules. Equipment manufacturers often state the RCD type required. Where they do, that instruction decides the choice. Check the current edition of BS 7671 for the exact requirements.
EV chargers and solar
Electric vehicle charging is the most common place a homeowner meets this question. A charging point needs protection against DC fault currents: either a Type B RCD, or a Type A (or F) RCD together with a device that detects 6 mA of DC, which many chargers have built in. Solar and battery inverters come with their own requirements in the installation manual.
Show the type on the plan
When you plan a new circuit, note the protective device against it: for example "C6 EV charger, 32 A, Type A RCBO plus 6 mA DC detection". In RoomPlot each cable route has its own colour and label, and a text note beside the consumer unit keeps the device choices on the same sheet as the layout.
Frequently asked questions
How do I tell which type of RCD I have?
Look for the symbol on the front of the device. Type AC shows a single sine wave in a box. Type A shows the sine wave with a pulsed wave below it. Types F and B add further symbols and are usually marked with the letter.
Do I have to replace my Type AC RCDs?
There is no blanket requirement to replace existing devices. An inspection may recommend improvement where Type AC protects circuits with DC-producing loads. New work should use the appropriate type.
Is an RCBO better than an RCD?
An RCBO protects a single circuit, so a fault trips only that circuit. A shared RCD protects several circuits at once, so one fault switches all of them off.
Free lesson. Want the full picture? Circuits explained is part of our free electrical floor plans course, with interactive exercises.