Bathroom Electrical Zones on a Floor Plan (BS 7671 Section 701)

Draw bathroom electrical zones on a floor plan: zone 0, 1 and 2, IP ratings, socket distances, shaver units and where switches and isolators go.

4 min read · 20 November 2026 · RoomPlot Team

Bathrooms are a special location in BS 7671 because water and electricity meet. The zones decide what can go where and which IP rating it needs, and drawing them on the plan is the quickest way to prove a design complies. This guide explains the zones and how to show them on a bathroom electrical plan.

The zones in plain terms

  • Zone 0 is the inside of the bath or shower tray. Equipment there needs at least IPX7 and is limited to SELV at no more than 12 V AC.
  • Zone 1 is the space directly above the bath or shower tray, up to 2.25 m above the floor. Where there is no tray, it extends 1.2 m horizontally from the fixed water outlet. Equipment needs at least IPX4, or IPX5 where water jets are used for cleaning.
  • Zone 2 extends 0.6 m horizontally beyond zone 1, again to 2.25 m. Equipment needs at least IPX4.
  • Outside the zones, ordinary accessories are allowed, subject to the socket rules below.
PLAN VIEW · ZONES 1 AND 2 RUN TO 2.25 M ABOVE THE FLOORHALL ZONE 1ZONE 2ZONE 1ZONE 2OUTSIDE ZONES Bathroom zones Plan view, BS 7671 Section 701 Zone 1: bath and shower tray IPX4 minimum, IPX5 for water jets Zone 2: 0.6 m beyond zone 1 IPX4 minimum Recessed ceiling light Rated for the zone it sits in Extractor fan Isolated from outside the room One-way switch Outside the room, or a pull cord Fused spur (fan isolator) In the hall, outside the zones Lighting cable route
Bathroom zones in plan view: zone 1 over the bath and the shower tray, zone 2 extending 0.6 m beyond, with the lights and fan rated for their zones and the controls outside in the hall.

Key takeaways

  • Zone 0 is inside the bath or shower tray, zone 1 is the space above it and zone 2 extends 0.6 m beyond zone 1.
  • Equipment in zones 1 and 2 needs at least IPX4.
  • Ordinary sockets must be at least 2.5 m from the zone 1 boundary under the amended 2018 edition.
  • Circuits serving a bathroom need 30 mA RCD protection.

Sockets, shavers and switches

Under the amended 2018 edition of BS 7671, socket-outlets other than SELV are not allowed within 2.5 m horizontally of the zone 1 boundary. Older guidance and the original 2018 text used 3 m, so check which edition applies to the work. A shaver supply unit to BS EN 61558-2-5 can sit in zone 2 where it is out of direct spray. Light switches are normally outside the room or operated by a pull cord, and the isolator for an extractor fan is usually a fused spur outside the room.

Protection and notification

Circuits serving a room containing a bath or shower need 30 mA RCD protection. Supplementary bonding can often be omitted when every circuit in the room is RCD protected and the other conditions in Section 701 are met. In England, new work in a bathroom is generally notifiable under Part P, so the plan you draw now becomes part of the paperwork.

Check the standard. Zone dimensions, IP ratings and socket distances here follow BS 7671:2018 Section 701 as amended. Confirm them against the current edition (BS 7671:2018+A4:2026 at the time of writing) before you design or certify.

Common mistakes

  • Treating zone 2 as outside the zones. It still needs IPX4 equipment and has its own rules.
  • Forgetting the shower without a tray. Zone 1 then extends 1.2 m from the fixed water outlet.
  • A 13 A socket by the basin. Use a shaver supply unit instead, and keep other sockets well away from zone 1.
  • The fan isolator inside the room. Put it outside, where it can be reached safely.

Drawing the zones in RoomPlot

Draw the bathroom with the bath and shower tray in position, then mark zone 1 over each and zone 2 around it with area zones, labelled with their names. Place recessed lights, the fan and any shaver unit, and route the lighting cable from the switch outside the room. The result is a single sheet that shows the client what goes where and shows the inspector why. See also our guide to drawing a bathroom floor plan, and more on our electricians page.

Frequently asked questions

Can I have a socket in a bathroom?

Only a shaver supply unit in a suitable position, or an ordinary socket at least 2.5 m horizontally from the edge of zone 1, which rules it out in most bathrooms.

What IP rating do bathroom lights need?

At least IPX4 in zones 1 and 2. Outside the zones no specific rating is set, but moisture-resistant fittings are a sensible choice.

Where does the bathroom light switch go?

Usually outside the room, or a ceiling pull cord inside it.

Free lesson. Want the full picture? Kitchens and bathrooms is part of our free electrical floor plans course, with interactive exercises.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read