An electric shower is one of the biggest single loads in a home. It heats water instantly, so it draws a lot of current for a short time, and it does that in a wet room. That is why it has its own circuit, its own isolator and its own rules.
Key takeaways
- An electric shower needs a dedicated circuit from the consumer unit, protected by a 30 mA RCD.
- Current is the shower's power divided by the voltage: a 9.5 kW shower draws about 41 A at 230 V.
- 10 mm² cable is the common choice, but the designer sizes it from the rating, route and length.
- A double-pole isolator must be easy to reach: a ceiling pull cord or a wall switch outside the bathroom zones.
Start with the rating
Divide the shower's kilowatt rating by the voltage to get the current it draws.
| Shower rating | Current at 230 V | Typical protective device |
|---|---|---|
| 7.5 kW | about 33 A | 40 A |
| 8.5 kW | about 37 A | 40 A |
| 9.5 kW | about 41 A | 45 A |
| 10.5 kW | about 46 A | 50 A |
These are typical pairings. The manufacturer's instructions state the required circuit rating for the model.
Cable size
Twin and earth cable of 10 mm² is the usual choice because it suits most showers and leaves room for a more powerful replacement later. A 6 mm² cable can be adequate for lower ratings on short runs. How the cable is installed matters: a cable buried in insulation carries much less current than one clipped to a joist. The designer checks current-carrying capacity and voltage drop for the actual route.
The isolator
A double-pole switch rated for the circuit, commonly 45 A or 50 A, lets the shower be isolated for maintenance. Inside the bathroom it is a ceiling-mounted pull cord. Outside, it can be a wall switch by the door. It must not be within reach of someone using the bath or shower.
RCD protection
Circuits serving a room with a bath or shower need 30 mA RCD protection. In a modern consumer unit that is an RCBO for the shower circuit alone.
Check the rules. A new shower circuit is notifiable work in England and Wales. The details here are a summary: check the manufacturer's instructions and the current edition of BS 7671.
Drawing it
- Place the consumer unit and the shower unit on the plan.
- Draw the cable route between them in its own colour, following the real path through the ceiling void or loft.
- Mark the isolator position and label it with its rating.
- Read the cable length from the route. RoomPlot adds up the length on plan as you draw, which is the starting point for the voltage drop check and the material order.
Frequently asked questions
Can a shower share a circuit with anything else?
No. An electric shower should be on its own dedicated circuit from the consumer unit.
Can I replace a shower with a more powerful one?
Only if the existing cable, protective device and isolator are adequate for the higher rating. An electrician should check before you buy.
Where does the pull cord go?
On the ceiling, out of reach of spray and where it is easy to find, typically near the bathroom door.
Free lesson. Want the full picture? Kitchens and bathrooms is part of our free electrical floor plans course, with interactive exercises.