Electric Shower Circuit: Cable Size, Isolator and How to Show It on a Plan

How an electric shower circuit is designed in the UK: kW rating and current, cable size, the 45 A double-pole isolator, RCD protection and the plan drawing.

3 min read · 21 November 2026 · RoomPlot Team

An electric shower is one of the biggest single loads in a home. It heats water instantly, so it draws a lot of current for a short time, and it does that in a wet room. That is why it has its own circuit, its own isolator and its own rules.

Shower 45 A DP Bathroom Landing Isolator: ceiling pull cord, or a switch outside the room Electric shower circuit Dedicated radial with a double-pole isolator Shower circuit Sized to the shower's kW rating Double-pole isolator Easy to reach, outside zones 0 to 2 Connection (switch to light) SYMBOLS Consumer Unit Recessed ceiling light One-way switch
A dedicated shower circuit: consumer unit, double-pole isolator outside the bathroom, then the shower unit.

Key takeaways

  • An electric shower needs a dedicated circuit from the consumer unit, protected by a 30 mA RCD.
  • Current is the shower's power divided by the voltage: a 9.5 kW shower draws about 41 A at 230 V.
  • 10 mm² cable is the common choice, but the designer sizes it from the rating, route and length.
  • A double-pole isolator must be easy to reach: a ceiling pull cord or a wall switch outside the bathroom zones.

Start with the rating

Divide the shower's kilowatt rating by the voltage to get the current it draws.

Shower ratingCurrent at 230 VTypical protective device
7.5 kWabout 33 A40 A
8.5 kWabout 37 A40 A
9.5 kWabout 41 A45 A
10.5 kWabout 46 A50 A

These are typical pairings. The manufacturer's instructions state the required circuit rating for the model.

Cable size

Twin and earth cable of 10 mm² is the usual choice because it suits most showers and leaves room for a more powerful replacement later. A 6 mm² cable can be adequate for lower ratings on short runs. How the cable is installed matters: a cable buried in insulation carries much less current than one clipped to a joist. The designer checks current-carrying capacity and voltage drop for the actual route.

The isolator

A double-pole switch rated for the circuit, commonly 45 A or 50 A, lets the shower be isolated for maintenance. Inside the bathroom it is a ceiling-mounted pull cord. Outside, it can be a wall switch by the door. It must not be within reach of someone using the bath or shower.

RCD protection

Circuits serving a room with a bath or shower need 30 mA RCD protection. In a modern consumer unit that is an RCBO for the shower circuit alone.

Check the rules. A new shower circuit is notifiable work in England and Wales. The details here are a summary: check the manufacturer's instructions and the current edition of BS 7671.

Drawing it

  1. Place the consumer unit and the shower unit on the plan.
  2. Draw the cable route between them in its own colour, following the real path through the ceiling void or loft.
  3. Mark the isolator position and label it with its rating.
  4. Read the cable length from the route. RoomPlot adds up the length on plan as you draw, which is the starting point for the voltage drop check and the material order.

Frequently asked questions

Can a shower share a circuit with anything else?

No. An electric shower should be on its own dedicated circuit from the consumer unit.

Can I replace a shower with a more powerful one?

Only if the existing cable, protective device and isolator are adequate for the higher rating. An electrician should check before you buy.

Where does the pull cord go?

On the ceiling, out of reach of spray and where it is easy to find, typically near the bathroom door.

Free lesson. Want the full picture? Kitchens and bathrooms is part of our free electrical floor plans course, with interactive exercises.

Sources

Plan it on your phone. Draw the shower circuit, read the cable length straight off the plan and export it for the certificate file. Download RoomPlot on the App Store and draw your first electrical plan in minutes, or see what it does on our electricians page.

Related guides

Electricians AFCI Requirements Explained: Which Rooms Need Arc-Fault Protection AFCI protection explained for US homes: what an arc fault is, the NEC 210.12 room list, what happens when you extend a circuit and how to plan it. 3 min read Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read