The breaker protects the wire. If the wire is too small for the breaker, it can overheat before the breaker trips. That one idea is behind every wire size chart. Here is the chart for typical copper conductors in a home, and the cases where you need to look further.
Key takeaways
- 14 AWG copper goes with a 15 A breaker, 12 AWG with 20 A and 10 AWG with 30 A.
- Smaller AWG numbers mean thicker wire.
- Larger circuits depend on the cable type and the temperature rating of the terminals.
- Long runs may need a larger size to limit voltage drop.
The small-conductor rule
For the three sizes used on most household circuits, NEC 240.4(D) sets the maximum breaker directly: 15 A for 14 AWG copper, 20 A for 12 AWG and 30 A for 10 AWG. These are the ones to memorise.
Larger circuits
Above 30 A, the size comes from the ampacity tables and depends on the insulation and how the cable is installed. Nonmetallic sheathed cable, the common house wiring cable, is limited to the 60 degree C column, so 6 AWG cable is good for 55 A, not 65 A. The same size conductors in conduit, connected to terminals rated for 75 degrees C, can carry more. That is why the chart shows two options for a 60 A circuit.
Aluminum
Aluminum conductors are common for services and large feeders. They need to be larger than copper for the same current, and the terminals must be rated for aluminum. The chart above is for copper.
Voltage drop
A long run loses voltage along the way. The NEC recommends, in an informational note, keeping the drop on a branch circuit to about 3%. A receptacle circuit to a detached garage 150 ft away may need 10 AWG where 12 AWG would do next to the panel. The length is the number you need, and it comes from the plan.
Check the rules. This chart is a quick reference for typical cases, not a design tool. Check the ampacity tables, terminal ratings, cable type and any derating in the edition of the NEC your jurisdiction enforces.
Reading cable markings
Cable labelled 12-2 has two insulated 12 AWG conductors plus a ground. 12-3 has three, used for three-way switch travelers and multiwire circuits. The sheath colour is a convention: white for 14 AWG, yellow for 12 AWG and orange for 10 AWG.
From plan to shopping list
Draw each circuit on the floor plan from the panel to its last outlet. RoomPlot totals the route length for each circuit, so you can check long runs for voltage drop and know how much of each cable size to buy. Label each route with its wire size and breaker, for example "C4, 12 AWG, 20 A".
Frequently asked questions
What size wire for a 20 amp circuit?
12 AWG copper.
Can I use 14 gauge wire on a 20 amp breaker?
No. 14 AWG copper is limited to a 15 A breaker.
What size wire for a 50 amp circuit?
Typically 6 AWG copper, subject to the cable type and terminal ratings.
Free lesson. Want the full picture? Cable routes and schedules is part of our free electrical floor plans course, with interactive exercises.
Sources
- NFPA 70, National Electrical Code: free online access and development
- NFPA: NEC adoption maps by state
- Electrical Safety Foundation International (ESFI)
Plan it on your phone. Measure every circuit length on the plan and order the right amount of each wire size. Download RoomPlot on the App Store and draw your first electrical plan in minutes, or see what it does on our electricians page.