Module 1 · Design calculations · Lesson 2 of 11

Cable sizing and correction factors

Free advanced lesson: size a cable from the design current, apply Ca, Cg, Ci and Cc, then check voltage drop, with an interactive derating calculator.

11 min · 0 XP · 0 of 11 lessons done

Lesson 2 of 11 All lessons
  1. 1Maximum demand and diversity
  2. 2Cable sizing and correction factors
  3. 3Fault protection, Zs and disconnection times
  4. 4US load calculations and wire sizing
  5. 5Three-phase supplies and load balancing
  6. 6Sub-mains and distribution boards
  7. 7Multi-storey plans, risers and fire stopping
  8. 8Solar PV and battery storage on the plan
  9. 9Data, alarm and power segregation
  10. 10Inspection records on plans
  11. 11Final test: advanced electrical floor plans

In this lesson

  • Ib ≤ In, then the cable must satisfy It ≥ In ÷ (Ca × Cg × Ci × Cc).
  • Grouping and insulation are the factors that change domestic cable sizes most often.
  • After the current check, voltage drop and fault protection can still change the size.

The tabulated rating of a cable assumes ideal conditions. Real routes are warm, crowded and insulated. This lesson turns the correction factors into a habit, then lets you try them live.

CORRECTION FACTORSWhat reduces a cable's current rating FACTOR WHAT IT COVERS TYPICAL VALUES Ca Ambient temperature 1.00 at 30 °C, 0.94 at 35 °C, 0.87 at 40 °C (70 °C thermoplastic cable) Cg Grouping with other loaded circuits 0.80 for 2 circuits, 0.70 for 3, 0.65 for 4 (bunched) Ci Thermal insulation around the cable 0.5 when surrounded for 0.5 m or more Cc Device type and buried cables 0.725 with a BS 3036 rewirable fuse, 0.9 for cables in the ground Required rating: It ≥ In ÷ (Ca × Cg × Ci × Cc). Values from BS 7671 Appendix 4: check the current tables.
The four correction factors and typical values.

The sizing sequence

  1. Find the design current Ib from the load.
  2. Choose a protective device In of at least Ib.
  3. Divide In by every correction factor that applies to get It.
  4. Pick the smallest cable whose rating for the installation method is at least It.
  5. Check voltage drop and fault protection.

A worked example

CABLE SIZINGSizing a 6.5 kW radial, step by step STEP WORKING RESULT 1. Design current Ib 6,500 W ÷ 230 V 28.3 A 2. Protective device In Next standard size above Ib B32, 32 A 3. Correction factors Bunched with two other circuits: Cg 0.70 0.70 4. Required rating It 32 ÷ 0.70 45.7 A 5. Choose the cable Twin and earth, clipped direct: 4 mm² is 37 A, too small 6 mm², 47 A 6. Voltage drop 7.3 mV/A/m × 28.3 A × 18 m 3.7 V, 1.6%: pass
Grouping with two other circuits moves a 6.5 kW radial from 4 mm² to 6 mm².

Read the route from the plan

Where the cable runs decides the factors: through a hot loft, bunched with other circuits along a joist, or buried in insulation. Draw the real route and the factors become obvious, and the route length is ready for the voltage drop check.

Values here are typical examples for teaching. Use the current BS 7671 Appendix 4 tables for the cable type and installation method on a real job.

Try it

Use the calculator to find the device and factors where 2.5 mm² is no longer enough for a 20 A radial.

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Cooker Circuit Guide: Cable Size, Diversity and the Cooker Switch UK cooker circuits explained: how diversity turns a 12 kW cooker into a 32 A circuit, typical cable sizes, where the cooker switch goes and how to draw it. 3 min read Electricians How to Estimate Cable Length from a Floor Plan Estimate cable length from a floor plan: measured run lengths per circuit, vertical drops, termination allowance and a margin, totalled for the quote. 3 min read