Ib ≤ In, then the cable must satisfy It ≥ In ÷ (Ca × Cg × Ci × Cc).
Grouping and insulation are the factors that change domestic cable sizes most often.
After the current check, voltage drop and fault protection can still change the size.
The tabulated rating of a cable assumes ideal conditions. Real routes are warm, crowded and insulated.
This lesson turns the correction factors into a habit, then lets you try them live.
The four correction factors and typical values.
The sizing sequence
Find the design current Ib from the load.
Choose a protective device In of at least Ib.
Divide In by every correction factor that applies to get It.
Pick the smallest cable whose rating for the installation method is at least It.
Check voltage drop and fault protection.
A worked example
Grouping with two other circuits moves a 6.5 kW radial from 4 mm² to 6 mm².
Read the route from the plan
Where the cable runs decides the factors: through a hot loft, bunched with other circuits along a joist, or buried
in insulation. Draw the real route and the factors become obvious, and the route length is ready for the voltage drop
check.
Values here are typical examples for teaching. Use the current BS 7671 Appendix 4 tables for the cable type and installation method on a real job.
Try it
Use the calculator to find the device and factors where 2.5 mm² is no longer enough for a 20 A radial.