Module 1 · Design calculations · Lesson 4 of 11

US load calculations and wire sizing

Free advanced lesson: the NEC standard-method dwelling load calculation, service sizing, energy management, and ampacity adjustment for crowded raceways.

11 min · 0 XP · 0 of 11 lessons done

Lesson 4 of 11 All lessons
  1. 1Maximum demand and diversity
  2. 2Cable sizing and correction factors
  3. 3Fault protection, Zs and disconnection times
  4. 4US load calculations and wire sizing
  5. 5Three-phase supplies and load balancing
  6. 6Sub-mains and distribution boards
  7. 7Multi-storey plans, risers and fire stopping
  8. 8Solar PV and battery storage on the plan
  9. 9Data, alarm and power segregation
  10. 10Inspection records on plans
  11. 11Final test: advanced electrical floor plans

In this lesson

  • Lighting and receptacles by floor area, plus small-appliance and laundry circuits, then demand factors.
  • Add the range, dryer, fixed appliances, heating or cooling, and EV charging to get the service size.
  • More than three current-carrying conductors in a raceway reduces each one's ampacity.

US projects add two calculations to the plan: the dwelling load calculation that sizes the service, and ampacity adjustment wherever several circuits share a raceway.

NEC LOAD CALCULATIONStandard method for a 2,000 sq ft house ITEM WORKING VA General lighting and receptacles 2,000 sq ft × 3 VA 6,000 Small-appliance circuits 2 × 1,500 VA 3,000 Laundry circuit 1 × 1,500 VA 1,500 Demand factor 3,000 at 100% + 7,500 at 35% 5,625 Range, 12 kW One range, Table 220.55 8,000 Dryer 5,000 VA minimum 5,000 Four fixed appliances 8,100 VA × 75% 6,075 Air conditioning Larger of heating or cooling 5,000 EV charger, 32 A 7,680 VA at 100% 7,680 Total 37,380 VA ÷ 240 V = 156 A 200 A service 2023 NEC. The 2026 edition moves these rules to Article 120 and uses 2 VA per sq ft for the service lighting load.
A worked standard-method calculation for a 2,000 sq ft house.

The standard method in five steps

  1. Floor area × 3 VA for general lighting and receptacles.
  2. Add 1,500 VA for each small-appliance circuit and the laundry circuit.
  3. Apply the demand factors: the first 3,000 VA at 100%, the next part at 35%.
  4. Add the range, dryer, fixed appliances, the larger of heating or cooling, and EV charging.
  5. Divide by 240 V and choose the service.

Service size and energy management

SERVICE SIZE100, 150 or 200 A? SERVICE TYPICAL HOME WATCH FOR 100 A Gas heating and cooking, no EV Little room for an EV charger or a heat pump 150 A Electric cooking and AC, a modest EV charger Run the load calculation before adding more 200 A All-electric: heat pump, electric cooking, EV charger The usual choice for new all-electric homes Any size, with load management Several large loads on a smaller service An energy management system can cap the calculated load The load calculation decides, not the rule of thumb. Energy management: NEC 220.70 in the 2023 edition.
Typical homes for each service size.

In the 2023 NEC, an energy management system that limits the load can be used in the calculation at its setpoint. That is often how an EV charger fits on an existing service.

Crowded raceways

AMPACITY ADJUSTMENTMore than three current-carrying conductors CONDUCTORS IN THE RACEWAY ADJUSTMENT 12 AWG THHN (30 A AT 90 °C) 4 to 6 80% 24 A 7 to 9 70% 21 A 10 to 20 50% 15 A: too small for 20 A 21 to 30 45% 13.5 A 31 to 40 40% 12 A 41 and above 35% 10.5 A Apply temperature correction too, e.g. × 0.91 at 40 °C for 90 °C wire. Small-conductor limits in 240.4(D) still apply.
Adjustment factors applied to 12 AWG THHN.

The 2026 NEC moves load calculations into Article 120 and lowers the service lighting load to 2 VA per square foot. Always use the edition your jurisdiction has adopted.

Try it

Take your own home's floor area and appliances and run the standard method. Which service size do you land on?

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Wire Size and Breaker Chart: Matching AWG to Amps in a US Home A simple US wire size and breaker chart: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A and up, with the reasons behind it and when to go larger. 3 min read