Free advanced lesson: the NEC standard-method dwelling load calculation, service sizing, energy management, and ampacity adjustment for crowded raceways.
Lighting and receptacles by floor area, plus small-appliance and laundry circuits, then demand factors.
Add the range, dryer, fixed appliances, heating or cooling, and EV charging to get the service size.
More than three current-carrying conductors in a raceway reduces each one's ampacity.
US projects add two calculations to the plan: the dwelling load calculation that sizes the service, and
ampacity adjustment wherever several circuits share a raceway.
A worked standard-method calculation for a 2,000 sq ft house.
The standard method in five steps
Floor area × 3 VA for general lighting and receptacles.
Add 1,500 VA for each small-appliance circuit and the laundry circuit.
Apply the demand factors: the first 3,000 VA at 100%, the next part at 35%.
Add the range, dryer, fixed appliances, the larger of heating or cooling, and EV charging.
Divide by 240 V and choose the service.
Service size and energy management
Typical homes for each service size.
In the 2023 NEC, an energy management system that limits the load can be used in the calculation at its setpoint.
That is often how an EV charger fits on an existing service.
Crowded raceways
Adjustment factors applied to 12 AWG THHN.
The 2026 NEC moves load calculations into Article 120 and lowers the service lighting load to 2 VA per
square foot. Always use the edition your jurisdiction has adopted.
Try it
Take your own home's floor area and appliances and run the standard method. Which service size do you land on?