Fault protection, Zs and disconnection times

Free advanced lesson: earth fault loop impedance, maximum Zs for B and C type breakers, 0.4 s and 5 s disconnection times, with an interactive Zs gauge.

9 min · 0 XP · 0 of 11 lessons done

Lesson 3 of 11 All lessons
  1. 1Maximum demand and diversity
  2. 2Cable sizing and correction factors
  3. 3Fault protection, Zs and disconnection times
  4. 4US load calculations and wire sizing
  5. 5Three-phase supplies and load balancing
  6. 6Sub-mains and distribution boards
  7. 7Multi-storey plans, risers and fire stopping
  8. 8Solar PV and battery storage on the plan
  9. 9Data, alarm and power segregation
  10. 10Inspection records on plans
  11. 11Final test: advanced electrical floor plans

In this lesson

  • Zs = Ze + (R1 + R2). Lower Zs means more fault current and a faster trip.
  • The maximum Zs is set by the current that trips the breaker instantly: 5 × In for type B, 10 × In for type C.
  • Long runs and small cables raise Zs, so check it at the design stage.

If a line conductor touches earthed metal, the protective device must switch off before anyone gets a dangerous shock. Whether it can depends on the earth fault loop impedance, Zs.

FAULT PROTECTIONDisconnection times and maximum Zs SITUATION TIME LIMIT EXAMPLE MAXIMUM ZS TN, final circuits: sockets up to 63 A, fixed equipment up to 32 A 0.4 s B6 7.28 Ω, B16 2.73 Ω, B32 1.37 Ω Type C breakers on those circuits 0.4 s C16 1.37 Ω, C32 0.68 Ω TN, distribution circuits and larger final circuits 5 s Depends on the device TT, the same final circuits 0.2 s Met with a 30 mA RCD Maximum Zs = 0.95 × 230 V ÷ the current that trips the breaker instantly. Compare measured values with about 80%.
Disconnection times and example maximum Zs values.

The loop

Fault current flows out along the line conductor, back along the protective conductor and through the supply. Zs is the impedance of that whole loop: Ze from the supply plus R1 + R2 from the circuit.

Breaker types

A type B breaker trips instantly somewhere between 3 and 5 times its rating, a type C between 5 and 10 times. To be sure, the fault current must reach the top of that band. That is why a C32 allows only half the Zs of a B32.

Design it in

R1 + R2 grows with length and shrinks with conductor size. Read the route length from the plan, estimate Zs before you install, and choose a larger cable or a shorter route if it is too high.

Try it

In the gauge, find the longest 2.5 mm² run a B32 allows on a TN-C-S supply, then switch to a C32 and see what changes.

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Earthing Systems Explained: TN-S, TN-C-S (PME) and TT TN-S, TN-C-S (PME) and TT earthing explained with a simple diagram: how to recognise each, why it matters for EV chargers and outbuildings, and what to record. 4 min read Electricians RCD Types Explained: AC, A, F and B, and Which One a Circuit Needs RCD types AC, A, F and B explained in plain English: what each detects, why Type AC is being phased out in UK homes and how to note the type on a plan. 3 min read