In this lesson
- Keep parallel runs apart or use a barrier.
- Cross at right angles, and use compartmented trunking when routes are shared.
- Give data and alarm cables their own colour and line style on the plan.
Data and alarm cables carry small signals at low voltage. Running them alongside mains cables risks interference and, if insulation fails, danger. Planning the separation costs nothing; fixing it later costs a lot.
The principles
- Keep a gap on parallel runs, commonly around 50 mm, or use a barrier or metal containment.
- Cross at right angles.
- Use separate compartments in shared trunking.
The rules
In the UK, BS 7671 requires separation between circuits of different voltage bands, and BS EN 50174-2 gives distances for data cabling. In the US, NEC 800.133 asks for 2 in (50 mm) unless a raceway or listed barrier separates them.
Try it
Sort the installation details above: which are fine as drawn, and which need separation or a barrier?