Module 1 · Design calculations · Lesson 1 of 11

Maximum demand and diversity

Free advanced lesson: work out a home's maximum demand with diversity, see why EV chargers get none, and test what fits on a 60, 80 or 100 A supply.

10 min · 0 XP · 0 of 11 lessons done

Lesson 1 of 11 All lessons
  1. 1Maximum demand and diversity
  2. 2Cable sizing and correction factors
  3. 3Fault protection, Zs and disconnection times
  4. 4US load calculations and wire sizing
  5. 5Three-phase supplies and load balancing
  6. 6Sub-mains and distribution boards
  7. 7Multi-storey plans, risers and fire stopping
  8. 8Solar PV and battery storage on the plan
  9. 9Data, alarm and power segregation
  10. 10Inspection records on plans
  11. 11Final test: advanced electrical floor plans

In this lesson

  • Maximum demand is the realistic peak current after diversity.
  • Diversity reduces lighting, second socket circuits and cookers, but not showers or EV chargers.
  • If the total beats the supply fuse, plan load management or an upgrade.

Every new big load starts with one question: can the supply take it? Maximum demand answers it. In this lesson you build a demand calculation for a real house and test what happens when the client wants a shower, an immersion heater and an EV charger as well.

MAXIMUM DEMANDA worked example for a house LOAD FULL CURRENT ALLOWANCE COUNTED Lighting, 1.2 kW connected 5.2 A About two thirds 3.5 A Socket ring 1 (largest) 32 A 100% 32.0 A Socket ring 2 32 A 40% 12.8 A Cooker 12 kW, socket on the control unit 52 A 10 A + 30% of the rest + 5 A 27.7 A Electric shower 9.5 kW 41 A 100% 41.3 A Immersion heater 3 kW 13 A 100% 13.0 A EV charger 7.4 kW 32 A 100%, no diversity 32.0 A Maximum demand 162 A Typical allowances from IET guidance. 162 A is well over a 100 A supply fuse: plan load management or an upgrade.
A worked example: diversity brings the total down, but the shower and EV charger still push past 100 A.

Connected load and diversity

The connected load is the sum of every rating. Real homes never draw that much at once, so designers apply diversity. Typical allowances from IET guidance: lighting at about two thirds, the largest socket circuit at 100% and the others at 40%, and a cooker at 10 A plus 30% of the rest, plus 5 A for a socket on the control unit.

Loads with no diversity

Instantaneous water heaters such as showers count the largest at 100%. Storage heaters, storage water heaters and EV chargers get no diversity at all. An EV charger only stops counting in full when load management controls it.

Compare with the supply

Most UK homes have a 60, 80 or 100 A main fuse. Write the result and the fuse rating next to the consumer unit on the plan, so the next person sees the decision.

Try it

Pick a house you know. List its circuits from the consumer unit labels and estimate the maximum demand with the allowances above.

Check your understanding

Official documents and further reading

Progress is saved in this browser.

Go deeper: related guides

Electricians Consumer Unit Replacement in the UK: What Is Involved and What a Good Quote Includes Replacing a fuse box in the UK: what a modern consumer unit includes, the testing and certificates involved, Part P notification and how a circuit plan helps. 4 min read Electricians EV Charger and Garage Electrical Plan: What to Draw Plan a garage with an EV charger: a dedicated charge point circuit, RCD and DC fault protection, garage sockets and lighting, drawn on a floor plan. 3 min read